|
By Charles Linn, FAIA
Efficiency counts: how the LTHP works
As the temperature starts getting near
freezing outside, the amount of heat that can be absorbed
by the liquid refrigerant boiling in the evaporator decreases.
This is because the pressure of the boiling liquid (measured
in pounds per square inch) inside the evaporator decreases,
and so does the density of the vapor (measured in pounds per
cubic foot) the boiling liquid turns into. This causes two
problems. First, the compressor has to work harder to pump
it because the pressure has dropped. Second, because the amount
of heat that vapor can carry is proportional to its density,
the compressor doesnt have the capacity to deliver sufficient
heat from the outside air to keep the inside of the building
warm. As the temperature continues to go down, the situation
worsens and, at 30 degrees Fahrenheit, the backup resistance
built into most air-source heat pumps turns on.
The most obvious way to solve the problem
would be to put a really big compressor into the system. But
when its not very cold outside, this overcapacity would
cause the system to be so inefficient that it would be counterproductive.
So instead, Shaw decided to add a second compressor, which
he calls a booster compressor (see page 164, diagram 2). This
is installed between the evaporator coil and what he calls
the primary compressorthe compressor thats already
present as standard equipment in every heat pump. Most of
the time, the booster compressor would be bypassed, and only
the primary would compress the vapor that is generated in
the evaporator. When the vapor pressure and density dropped
below a certain point, however, the booster compressor would
be allowed to come on if the outdoor air temperature had dropped
below a certain point and the thermostat inside the building
is also calling for more heat. The booster compressor has
a much larger displacement than the typical primary compressor,
so when it is enabled, it can move many more cubic feet of
vapor per minute. The LHTPs performance can be enhanced
in the future when variable speed booster compressors are
introduced.
 |
| The top graph shows
how well different parts of an LTHP keep up
as the temperature drops. With everything
running, an LTHP keeps up with heating load
until 0 degrees Fahrenheit, while conventional
heat pumps bottom out at 25 degrees. The graph
at right shows coefficients of performance.
At 0 degrees, the LTHP makes twice as much
heat per unit of electricity input as the
conventional heat pump. |
 |
|
|
Shaw also knew that in most heat pumps,
even after the liquid refrigerant has given up much of its
heat to the condenser, it is still pretty warm. When it gets
really cold outside, this warmth causes as much as 40 percent
of that liquid to vaporize as it goes through the expansion
valve. It would be better if it cooled first. That way, more
of the refrigerant would remain in liquid form, so it could
be boiled later on in the evaporator coil, where it absorbs
heat from the outside air while changing states. Shaw figured
that one way to cool the refrigerant would be to donate
some of its surplus heat to a process that would create a
source of high-density vapor that would bypass the evaporator
coil altogether and be sent directly to the primary compressor.
Shaw calls the device he uses to do this
a subcooling economizer (see page 165, diagram 3). It is a
heat exchanger that is placed between the condenser and the
expansion valve. It splits the refrigerant liquid coming from
the condenser into two streams. The majority of the refrigerant
passes through one side of the heat exchanger, where it gives
up the heat necessary to vaporize a smaller stream of refrigerant
being fed into the other side of the exchanger. This vapor
is then sent to a point between the booster compressor and
the primary compressor, while the larger stream of liquid
refrigerant, now cooled significantly, is sent through the
expansion valve and on to the evaporator coil, where it boils
into vapor.
|