|
Creating Code-Compliant Designs
Advertising supplement provided by
National Gypsum Company
Analyzing the Assembly: Find No.
L558
What follows is an analysis and discussion of the details
of one of the UL's fire-resistant assemblies from a seminar
presented by Rich Picolo and Missy Merfeld. Use the UL Directory's
Numbering System for Fire Rated Assemblies Chart.
Question: What is an assembly number for a wooden floor system
using drywall?
In the first column of the Numbering Systems for Fire Rated
Assemblies chart, select the type of construction and then
look across for the series with gypsum board. You should come
up with the letter designation L or N for wood joist, and
500 to 599 series. Let's pick assembly number 558 as an example
to review. Refer to the drawing of the assembly and the information
that is typical of the detail you will find in the fire systems
manual. We will talk briefly about things important to note
in specification, and in subsequent construction.
L558 is an unrestrained assembly. Depending on which part
of the country you are from, some of the codes, for example
the uniform code, are very particular about where you have
to use restrained or unrestrained systems. BOCA does not delineate
it, but as a rule of thumb, when you specify an assembly,
you must specify whether you want to construct it as a restrained
or an unrestrained assembly. This may affect how an assembly
performs during a fire; sometimes you will need additional
drywall in some assemblies.
The assembly has a finish rating. We have a 1-hour assembly
but the finish rating is only 23 minutes. Here is what a finish-rating
means: When we test assemblies we look for a couple of critical
temperatures---an average temperature of no more than 250
degrees and hot spots no greater than 325 degrees. The finish
rating is the point at which those temperatures are reached
on one side of the assembly. BOCA or IBC never discuss finish
ratings. If you go to NFPA 101, they do talk about finish
ratings. So depending on what code the municipality uses,
finish rating may or may not be critical.
Let's continue to go through the assembly L558. It starts
with the flooring system. The finished flooring may consist
of any one of the four systems listed in the UL design . We
will 1 floor system to study.
From L558: The nominal 1 x 4 tongue and groove is laid perpendicular
to the trusses, 15/32 in thick wood structural panels, minimum
grade underlayment, or single floor. This tells us certain
types and thickness of material we must use that must be laid
perpendicular to the trusses. It does not say plywood , this
is a relatively new assembly; it says wood structural panels.
Some other designs still say plywood; some say wood structural
panels. The long dimensions of the panel are to be perpendicular
to the truss with the joints staggered. The staggering of
the joints is common construction procedure. It's even more
important, however, in a fire-rated assembly, because if you
put all the joints in one spot there is a bigger chance of
heat spread, and a bigger chance of failure during the course
of the test.
A vapor barrier is optional, but if a vapor barrier is used,
it must be a commercial asphalt-saturated felt, not Visqueen.
That is a horrible mistake that is made in the field, whether
it is specified that way or done by the contractor. That is
why it is important that the UL details are put directly on
your plans. The contractor will then know what he is supposed
to bid and what he is supposed to build.
Sub-flooring: 23/32 in-thick wood structural panels installed
perpendicular to the trusses with the end joints staggered.
Nails: spaced 12 inches on center along each truss. You can
use staples but they have to be equal or greater withdrawal
and lateral resistance and strength. So you can use staples
but the burden of proof will be on you that it is equivalent
to the nails specified.
Trusses: Parallel chord, so we can't use this as a floor-ceiling
assembly. Maximum 24-in OC with fabricated nominal 2 x 4 lumber.
'Can I go with a spacing wider than 24 in.?' No you cannot.
'Can I go less than 24?' Yes you can. Minimum truss depth
is 18 inches. You can go deeper (suppose you have mechanical
equipment or duct work to install), but you can not go less
than 18 inches. That has to do with heat transfer. It says
no less than 18, you can't use12-inch trusses. Make sure that
the truss manufacturer who bids this job knows about the truss
plate requirements. Batt and blanket insulation: This assembly
does show insulation: glass fiber, maximum of 3 ½ in.
You can't use six inches. There are some exceptions, but basically
you must follow what it says. Fitted in the concealed space,
draped over the resilient channels, and gypsum wallboard membrane.
Can I use a sprayed cellulose insulation? No, it says fiberglass.
The insulation also has to bear the UL classification mark.
That means it has passed certain surface-burning and certain
fire-resistance rating. There is an exception where you can
use loose fill insulation, but the loose fill has to have
the UL classification mark. Air Duct: You can use any UL Class
0 or Class 1 flexible air ducts. They have to be installed
according to the manufacturer's installation instruction.
That is critical, since when they run these assembles through
the test, everything is installed according to the manufacturer's
instruction. Ceiling damper:
is not a fire damper. It
has no hourly rating. It's just listed as a ceiling damper,
maximum size 324 inches, no more than 18 x 18, maximum height
14 inches, and installed per the manufacturer instructions.
But, it is critical if you are doing a ceiling damper, no
more than 324 sq. inches in any 100 sq. feet. You can't put
two of them next to each other.
Furring channels: gives you the size of the furring channel,
depth of the channel, the space of the channel, types of screws
to be used, how far to overlap, this is critical in the installation.
If you don't follow this, the assembly may fail in a fire.
Gypsum board: Here it tells us that we use nominal 5/8 inch
gypsum board, 48 inches wide, installed in the long dimension
perpendicular to the resilient channels. It tells you which
way the drywall has to run. It tells you 1-1/8in- long, type
S screws every 12 inches. Also, it tells you how far from
the side joint and how far from the end joint you have to
put the screw. If you don't follow this, it does not meet
the assembly specifications. The drywall may fail sooner into
the fire. Once the drywall fails, it exposes the assembly
to the fire and the assembly will fail quickly. When insulation
is installed, it must be draped over the channel, over the
sitting member and the screws shall be installed 8 inches
on center, and here it says we must use a certain type of
drywall. It says FSW-C. This is a Type C drywall. You can't
use Type X drywall with this assembly. You must use Type C.
When the directory specifies a product, it's the only one
that can be used.
Finishing system: It is not shown in the assembly, but it
has vinyl, dry or premixed compound applied two coats to the
joints. In this particular assembly, even though page 1 says
a minimum of 1 coat, this assembly says 2 coats applied to
the joints. So this is more specific, and the specific always
overrules the general. So if an assembly has a specific requirement,
it will always overrule the general requirement.
|